123kV GIS/Transformer Termination

Applicable to connect extruding HV cables to GIS equipment and transformer,it is suitable for  XLPE or EPR insulated cables with copper, aluminum or aluminum alloy conductors.

Voltage (kV)

123
Insulation Diameter(mm)

Φ50~Φ104

Cross section Area of cable conductor(mm2)

240-2000mm2
The conductor connection method

Crimping

Bolt shear

Technical data:

Testing items

Testing contentsValue
AC withstand TestDry AC withstand test

160kV 15min

Impulse test

Lightning impulse550kV,±10 times

 

Current carrying capacityRated current

Short-circuit current

By cable spec

Stress cone electrical

 performance

AC withstand test

Partial discharge test

160kV 30min

As 96kV,≤5pC

The information of dimension and weight

Product’s Type

The height (mm)The weight (kG)
Short Type1150

55

Long Type

1430

75