145kV GIS/Transformer Termination

Applicable to connect extruding HV cables to GIS equipment and transformer,it is suitable for  XLPE or EPR insulated cables with copper, aluminum or aluminum alloy conductors.

Voltage (kV)145
Insulation Diameter(mm)Φ50~Φ104
Cross section Area of cable conductor(mm2)240-2500mm²
The conductor connection methodCrimping Bolt shear
 
Testing itemsTesting contentsvalue
AC withstand TestDry AC withstand test190kV 15min
Impulse testLightning impulse650kV, ±10 times
Current carrying capacityRate current
Short-circuit current
By cable spec
Stress cone electrical
performance
AC withstand test
Partial discharge test
190kV 30min
As 114kV,≤5pC

The information of dimension and weight

Product’s TypeThe height (mm)The weight (kG)
Short Type115055
Long Type143075

Applicable to connect extruding HV cables to GIS equipment and transformer,it is suitable for  XLPE or EPR insulated cables with copper, aluminum or aluminum alloy conductors.