245kV GIS/Transformer Termination

Applicable to connect extruding HV cables to GIS equipment and transformer,it is suitable for  XLPE or EPR insulated cables with copper, aluminum or aluminum alloy conductors.

Voltage (kV)245
Insulation Diameter(mm)Φ80.6~Φ125.6
Cross section Area of cable conductor(mm2)400-3500mm²
The conductor connection methodCrimping Bolt shear
 
Testing itemsTesting contentsvalue
AC withstand TestDry AC withstand test254kV 15min
Impulse testLightning impulse1050kV, ±10 times
Current carrying capacityRate current
Short-circuit current
By cable spec
Stress cone electrical
performance
AC withstand test
Partial discharge test
318kV 30min
As 190kV,≤5pC

The information of dimension and weight

Produit’s TypeThe height (mm)The weight (kG)
Short Type1350155
Long Type1700165