72.5kV GIS/Transformer Termination

Applicable to connect extruding HV cables to GIS equipment and transformer,it is suitable for  XLPE or EPR insulated cables with copper, aluminum or aluminum alloy conductors.

Voltage (kV)72.5
Insulation Diameter(mm)Φ47~Φ87.6
Cross section Area of cable conductor(mm2)185-2000mm²
The conductor connection methodCrimping Bolt shear
 
Testing itemsTesting contentsvalue
AC withstand TestDry AC withstand test125kV 15min
Impulse testLightning impulse450kV, ±10 times
Current carrying capacityRate current
Short-circuit current
By cable spec
Stress cone electrical
performance
AC withstand test
Partial discharge test
125kV 30min
As 75kV,≤5pC

The information of dimension and weight

Produit’s TypeThe height (mm)The weight (kG)
Short Type115055
Long Type143075

Applicable to connect extruding HV cables to GIS equipment and transformer,it is suitable for  XLPE or EPR insulated cables with copper, aluminum or aluminum alloy conductors.