Applicable to connect the extruding HV cables each other, suitable for XLPE or EPR insulated cables with copper, aluminum or aluminum alloy conductors.
| Voltage (kV) | 72.5 |
| Insulation Diameter(mm) | Φ47~Φ87.6 |
| Cross section Area of cable conductor(mm2) | 185-2000mm² |
| The conductor connection method | Crimping Bolt shear |
| Testing items | Testing contents | value |
| AC withstand Test | Dry AC withstand test | 125kV 15min |
| Impulse test | Lightning impulse | 450kV, ±10 times |
| Current carrying capacity | Rate current Short-circuit current | By cable spec |
| Stress cone electrical performance | AC withstand test Partial discharge test | 125kV 30min As 75kV,≤5pC |
| Shield interruption test | Lightning Impulse test DC withstand test | 30kV,±10 times 25kV 1min |
The information of dimension and weight
The length with copper housing:1500mm,the weight with copper housing:70kg;
The length with copper housing/coffin box:2200mm,
the weight with copper housing/coffin box:150kg
Applicable to connect the extruding HV cables each other, suitable for XLPE or EPR insulated cables with copper, aluminum or aluminum alloy conductors.